AQUASNAP 30RB060-390Air-Cooled Liquid Chillers with COMFORTLINK Controls60 HzWiring DiagramsUNITS WITH STARTING SERIAL NUMBER 3507QINDEX*30RB Unit Size060-100110-190210-300VoltageAllAllAll30RB Unit SizeVoltage060-080All090, 100All110-150All160-190All210-300All30RB Unit Size208/230080-120380, 460, 575208/230130-190380, 460, 575with Terminal Block (Standard)380, 460, 575with Non-FusedDisconnect Option208/230210, 225380, 460, 575with Terminal Block (Standard)380, 460, 575with Non-FusedDisconnect Option208/230250-300380, 460, 57530RB Unit SizeVoltage060-300AllCONTROL SCHEMATICSFigure Number456567879Voltage208/230380, 460, 575060,070POWER SCHEMATICSFigure Number123COMPONENT ARRANGEMENTSConnectionsControl Box onControlFan rolFan ElectricalPower-LPowerPE1ControlFan ElectricalPowerPE1ControlFan ElectricalPE1PowerPower-LControlFan ElectricalPower-LPowerPE1PE2ControlFan ElectricalPowerPE1ControlFan ElectricalPE1PowerPower-LControlFan ElectricalPower-LPowerPE1PE2ControlFan ElectricalPE1PowerPE2FIELD WIRINGPower/ControlFigure NumberConnections18Schematic19Label 0ALabel 029800AFigure 12131516121417Label F805096SF805097SF805090SF805092SF805093Label Diagram—00DCN5001300A* See Table 1 for modular sizes.Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-56300002-01Printed in U.S.A.Form 30RB-3WPg 112-08Replaces: New
NOTE: For operating sequence, refer to the Controls, Start-Up,Operation, Service, and Troubleshooting literature.GENERALThis publication contains Wiring Diagram information forthe 30RB060-390 air-cooled liquid chillers with electroniccontrols. These chillers are equipped with ComfortLink controls and electronic expansion valves.NOTE: Unit sizes 315-390 are modular units that are shippedin separate sections as modules A or B as noted in position 8 ofthe unit model nomenclature. See Table 1 for a listing of unitsizes and modular combinations.NOTE: The nameplate for modular units contains only the firsttwo digits in the model number. For example, 315A and 315Bname plates read 31A and 31B.SAFETY CONSIDERATIONSInstalling, starting up, and servicing this equipment can behazardous due to system pressures, electrical components, andequipment location (roof, elevated structures, etc.). Onlytrained, qualified installers and service technicians shouldinstall, start up, and service this equipment. When working onthis equipment, observe precautions in the literature, and ontags, stickers, and labels attached to the equipment, and anyother safety precautions that apply. Follow all safety codes.Wear safety glasses and work gloves. Use care in handling,rigging and setting this equipment, and in handling all electrical components.Table 1 — Modular Unit CombinationsMODULAR NGElectrical shock can cause personal injury and death. Shutoff all power to this equipment during installation andservice. There may be more than one disconnect switch.Tag all disconnect locations to alert others not to restorepower until work is completed.MODULE A30RBA16030RBA17030RBA17030RBA19030RBA190MODULE B30RBA16030RBA16030RBA17030RBA17030RBA190NOTE: An “A” in the fifth position of the model number indicates thedesign series.2
LEGENDALM RALT larm RelayAlert RelayContactor, CompressorCircuit Breaker/DisconnectCompressor Crankcase HeaterCooler HeaterCompressorChilled Water Flow SwitchChilled Water PumpDischarge Line Solenoid ValveDischarge Pressure TransducerEquipmentElectronic Expansion ValveEnergy Management ModuleFan BoardFan ContactorFactory-Installed OptionFan MotorFanFuseGround Fault Interrupter — Convenience OutletGroundHand/Off/AutoHand/Off/Auto, Auto SettingHand/Off/Auto, Hand SettingHigh-Pressure SwitchLeaving Water TemperatureMain Base BoardMinimum Load ValveLow Ambient Temperature Head Pressure ControlMotorNational Electrical Code (U.S.A.)Outdoor Air TemperaturePMPPMPIRDY RRRBRRCRRTRUN RSGTSHD ——————Pump, Chilled WaterChilled Water Pump InterlockReady RelayReverse Rotation BoardReverse Rotation ContactReverse Rotation TimerRun RelaySuction Gas ThermistorShutdown RelayScroll Protection ModuleSuction Pressure TransducerSwitchThermistorTerminal BlockTemperatureTransformerTerminal Block ConnectionMarked TerminalUnmarked TerminalUnmarked SpliceFactory WiringOptional WiringIndicates common potential.Does not represent wiring.FIOP or AccessoryWire TagNOTES1.2.3.4.5.6.7.8.Factory wiring is in accordance with Underwriters Laboratories (UL) 1995 standards. Field modifications or additions must bein compliance with all applicable codes.Wiring for main field supply must be rated 75 C minimum. Use copper for all units.Incoming wire size range for the terminal block is no. 4 American Wire Gage (AWG) to 500 kcmil.Incoming wire size range of non-fused disconnect with Minimum Circuit Amps (MCA) up to 599.9 amps is 3/0 to 500 kcmil.Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is 1/0 to 500 kcmil.Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is 250 to 500 kcmil.Terminals 9 and 10 of TB5 are for field external connections for remote on-off. The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA.Terminals 1 and 2 of TB5 are for external connections of chilled water pump interlock. The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA.Terminals 11 and 13 of TB5 are for control of chilled water pump 1 (PMP1) starter.Terminals 13 and 15 of TB5 are for control of chilled water pump 2 (PMP2) starter.The maximum load allowed for the chilled water pump relay is a 5 va sealed, 10 va inrush at 24 v. Field power supply is notrequired.For control of chilled water pumps, a set of normally open contacts rated for dry circuit application must be supplied from fieldsupplied pump starter relay. Connect contacts to violet and pink wires in harness from main base board channel 18. Wires inharness are marked PMP1-13 and PMP1-14.Terminals 12 and 13 of TB5 are for an alarm relay. The maximum load allowed for the alarm relay is 10 va sealed, 24 va inrushat 24 v. Field power supply is not required.Make appropriate connections to TB6 as shown for energy management board options. The contacts for occupancy override,demand limit and ice done options must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA.3
** Units with dual pointpower option have2 reverse rotation boards.COOLER HEATER OPTIONa30-4560PUMP OPTIONFig. 1 — Power Schematic, 30RB060-100 (All Voltages)4
a30-4654Fig. 2 — Power Schematic, 30RB110-190 (All Voltages)5
** For 380, 460, and 575-v units in sizes 250-300 there are2 RRBs: one in the Fan Electrical Box and one in PE2. For208/230-v units in sizes 210-300, there are 3 RRBs: one inthe Fan Electrical Box, one in PE1 and one in PE2.a30-4655Fig. 3 — Power Schematic, 30RB210-300 (All Voltages)6
**COMPRESSOR ANDFAN LOCATIONSa30-4563*Field-Supplied.Fig. 4 — Control Schematic, 30RB060-080 (All Voltages)7
*** HPS is located on last compressor incircuit for each unit.SEE FIG. 8 FOR MOREHOA WIRING DETAILSa30-4564Fig. 5 — Control Schematic, 30RB060-100 (All Voltages)8
a30-4656Fig. 6 — Control Schematic, 30RB090-150 (All Voltages)9
*** HPS is located on last compressor incircuit for each unit.a30-4566Fig. 7 — Control Schematic, 30RB110-190 (All Voltages)10
a30-4657Fig. 8 — Control Schematic, 30RB160-190 (All Voltages)11
a30-4658Fig. 9 — Control Schematic, 30RB210-300 (All Circuits)12
**** HPS is located on lastcompressor in circuit foreach unit.a30-4569Fig. 9 — Control Schematic, 30RB210-300 (All Circuits) (cont)13
a30-4570Fig. 10 — Component Arrangement, Combination Box, 30RB060, 070 (208/230 v)14
a30-4571Fig. 11 — Component Arrangement, Combination Box, 30RB060-120 (380, 460 and 575 v)15
a30-457216Fig. 12 — Component Arrangement, Fan Electrical Box 30RB080-120 (208/230 v); 30RB130-300 (All Voltages)
a30-4573STANDARDTERMINALBLOCKFig. 13 — Component Arrangement, Power-L Box 30RB080-300 (208/230 v); 130-225(380, 460 and 575 v with Non-Fused Disconnect Option)17
18Fig. 14 — Component Arrangement, Power Electrical Box 1, 30RB130-300 (380, 460, and 575 v with Terminal Block or Non-Fused Disconnect Option)a30-4574
a30-457519STANDARDTERMINALBLOCKFig. 15 — Component Arrangement, Power Electrical Box 1, 30RB130-300 (208/230 v)
a30-457620Fig. 16 — Component Arrangement, Power Electrical Box 2, 30RB210-300 (208/230 v)
a30-457721Fig. 17 — Component Arrangement, Power Electrical Box 2, 30RB250-300 (380, 460 and 575 v)
DISPLAYLOCATIONSIZE 060, 070ALL VOLTAGESSIZE 080-120380, 460, 575 VFIELD CONTROLWIRING ENTRYELECFANTRICALCOMBINATIONOR POWER-LSIZE 080-120,208/230 VSIZE 130-300,ALL VOLTAGESFIELD CONTROLWIRING ENTRYERPOW ICALTRCELE1ERPOW ICALRTCEEL2MAIN POWER ENTRANCEDISPLAYLOCATIONMAIN POWER ENTRANCEMAIN POWER ENTRANCETYPICAL CONTROL BOX LOCATIONSAND MAIN POWER ENTRYFig. 18 — Field Wiring Connections – All 30RB Units (See Table 2)22
Table 2 – Field Wiring Connections and Control Boxes30RB UNITSIZEVOLTAGEELECTRICAL OPTIONCONNECTIONSSingle Point060,070208/230, 380,380, 460, 575Standard (Terminal Block)Dual PointNon-Fused Disconnect Option*208/230Single PointSingle PointStandard (Terminal Block)Dual PointNon-Fused Disconnect Option*080-120380, 460, 575Single PointSingle PointStandard (Terminal Block)Dual PointNon-Fused Disconnect Option*Single PointSingle PointStandard (Terminal Block)Dual Point208/230Single PointNon-Fused Disconnect OptionDual Point130-190Single PointStandard (Terminal Block)Dual Point380, 460, 575Single PointNon-Fused Disconnect OptionDual PointStandard (Terminal Block)Dual PointNon-Fused Disconnect OptionDual Point208/230†Single Point210, 225Standard (Terminal Block)Dual Point380, 460, 575Single PointNon-Fused Disconnect OptionDual PointStandard (Terminal Block)Dual PointNon-Fused Disconnect OptionDual Point208/230†Single Point250-300Standard (Terminal Block)Dual Point380, 460, 575Single PointNon-Fused DisconnectDual Point*Dual point connection is not available when non-fused disconnect option is selected.†Single point connection not available.23MAIN POWERENTRANCECircuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 2Circuit 1Circuit 2Circuit 1Circuit 2Circuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 2Circuit 1Circuit 2Circuit 1Circuit 2Circuit 1Circuit 1Circuit 2Circuit 1Circuit 1Circuit 2CONTROL E1PE2
Fig. 19 — Field Wiring Schematic, All 30RB yright 2008 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-56300002-01Printed in U.S.A.Form 30RB-3WPg 2412-08Replaces: New
1. Factory wiring is in accordance with Underwriters Laboratories (UL) 1995 standards. Field modifications or additions must be in compliance with all applicable codes. 2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Incoming wire size range for the terminal block is no. 4 American Wire Gage (AWG) to 500 kcmil.