Transcription

CT Saturation in Industrial Applications – Analysis and Application GuidelinesCT Saturation in Industrial Applications –Analysis and Application GuidelinesBogdan Kasztenny, Manager, Protection & Systems Engineering, GE MultilinJeff Mazereeuw, Global Technology Manager, GE MultilinKent Jones, Technology Manager, GE Multilin - Instrument Transformers Inc (ITI)1. IntroductionIt is possible that relatively low-ratio CTs are applied for protective relaying of small loadsfed from switchgear and motor controllers of relatively high short-circuit capacity. Assumethe worst-case scenario of 64kA available fault current from bus feeding a small motor loadof normal current below 50A. In theory, CTs rated as lows as 50:5 and relay class C10 maybe applied for protection purposes.Realizing that 64kA of fault current is 1080 times the rated current of the 50:5 CT, themagnitude of the problem is evident. Protection class CTs are designed to work in the linearrange, with minimal errors and minimal waveform distortion, only up to 20 times the ratednominal current with the burden as defined by the relay class (saturation voltage) of the CTper IEEE Std. C57.13.Well-established and relatively accurate equations are available for calculation of theactual maximum primary current for saturation-free operation under any specific burden,any specific X/R ratio, and any specific residual flux in the CTs. This engineering practice is oflittle help here: A CT fed with a primary current hundreds of times its rated current willsaturate severely - only relatively short duration peaks of limited current will be observedfrom the secondary of the CT. These peaks can be as low as 5-10% of the ratio current, andwill last a small fraction of the half-cycle, down to 1-2ms in extreme cases. As a result only avery small portion of the actual ratio current is presented to protective relays fed from suchseverely saturated CTs. In terms of the true RMS value, the secondary current may be as lowas 1-2% of the expected RMS secondary current.1 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application GuidelinesOn the surface it may seem that a severe problem takes place here – the fault current isso high that it virtually stops the CT from passing the signal to the relay. The relay does notsee enough proportional secondary current during severe faults in order to operate its shortcircuit protection. The upstream relay, using CTs of a much higher ratio, measures the faultcurrent more accurately and trips. Zone selectivity is lost because the poor low-ratio CT was“blinded” to the fault.It is justified to assume that vast majority of industrial applications are not supported bycomputer simulation studies (EMTP) of saturated CTs, or any lengthy and sophisticated CTanalysis. At the same time there is a population of relays installed on high capacity busesand fed from low ratio CTs. An obvious question arises: why does the above problem notdemonstrate itself in the field?In this paper we will analyze the problem in detail and explain its underlying mechanics.Several GE Multilin’s relays are analyzed in terms of their response to heavily saturatedwaveforms. A formal, compact and easy to grasp method is shown to present complexrelations between the CT response and the response of any given relay. Based on thisgraphical method one can quickly evaluate the problem (do I have a problem when usingrelay X, with CT Y, under fault capacity Z, and overcurrent pickup setting Q?), and clearly seealternative solutions if a problem truly exists (i.e. definition of a method to match relays withCTs).This paper illustrates that many unknowns in analysis do not have significant impact onthe outcome. Reasonable conclusions will be evident from the results, even though broadassumptions are made in the model.This exploratory analysis shows that severely saturated CTs only slightly reduce shortcircuit tripping capabilities of GE Multilin’s relays. Given the typically applied settings, there isno danger of a failure to trip from intantenous overcurrent functions even in extreme casesof very high short-circuit currents and low-ratio CTs.2. Severe Saturation of Low-Ratio CTsWell-established engineering practice exists for CT selection to ensure saturation freeoperation of protection CTs at a given short circuit level, CT burden, X/R ratio and assumedresidual flux. In the context of this paper, it is assumed that this engineering technique is notapplied, and severe saturation will occur for short circuits within the protected zone (motor,feeder, cable or bus).Analytical analysis of a saturated CT is not practical. Only “time to saturation” may beapproximated with relative ease, and is used in some protection applications. More detailedanalytical analysis is not in the realm of practical engineering.Computer simulations are the only efficient way to extract the required information onsecondary signals. These are burdensome for everyday engineering in the industrial domain.This paper uses computer simulation to derive simple and practical analysis and engineeringcharts to address the problem.2 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application GuidelinesFigures 1 and 2 below present plots of the proportional secondary CT current, and thesimulated secondary current for a 50:5, C10, CT with a 0.2ohm resistive burden under thefault current of 10 times nominal current (without and with full dc offset, respectively). Thispoor performance CT with this particular burden saturates slightly under 500A ac current(Figure 1), and accordingly more when full dc offset is present in the primary current (Figure2). This document uses a digital model of a CT. More information on the model and itsvalidation can be found in Section 7.Figures 3 and 4 present the performance of the same CT under the fault current of 200times the nominal, i.e. 10kA. Now, the saturation is much more severe.This paper focuses on extreme cases of CT saturation, with primary current as high as1000 times the rated value. Figures 5a through 6b present a series of secondary currentssuperimposed on the ratio current. The primary current ranges from 200 to 1500 times theCT rating (10kA to 75kA in this case). All traces are rescaled to the peak of the ratio currentfor easy visualization (in this way all currents have the same graphical scale). Figure 5 is forsymmetrical currents, and Figure 6 for the fully offset currents.These figures illustrate severity of the problem. The secondary current is as low as 5-8%of the expected ratio current, and exhibits spikes shorter than 1ms when the fault current isas high as 75kA. Please note that this 50:5, C10, CT has a burden of 0.2ohms, virtuallymaking it into an IEEE C57.13 “C5 relay class” equivalent.It is important to observe that the secondary current, despite being extremely lowcompared with the fault current, is still very large compared with the CT and relay ratings:For example, consider a fully offset 75kA current and a 50:5, C10, CT of Figure 6b. Thepeak value of the secondary current is only about 5% of the peak value of the faultcurrent, but this translates to 0.05*75kA* 2 / (50:5) 530A peak secondary, or 530Apeak/( 2 *5A) 75 times rated value of the relay. This is a substantial currentconsidering a typical conversion range of a microprocessor-based relay is 20-50times the rated current. Figure 7 shows the relation between the peak value of thesecondary current, and peak value of the ratio current for the simulated CT (10kA75kA range).Consider however, that it is the short duration of the peaks of the secondary current, notthe low magnitude of those peaks that is important from the point of view of the signalstrength delivered to the relay.3 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines10.80.6SECONDARYCURRENTCurrent, pu of .010.020.030.04time, sec0.050.060.070.08Fig.1. 50:5, C10, CT with a burden of 0.2ohms under fault current of 500A NTCurrent, pu of fault10.50-0.5-100.010.020.030.04time, sec0.050.060.070.08Fig.2. 50:5, C10, CT with a burden of 0.2ohms under fault current of 500A (fully offset).4 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines10.8RATIOCURRENT(10kA)0.6Current, pu of 10.020.030.04time, sec0.050.060.070.08Fig.3. 50:5, C10, CT with a burden of 0.2ohms under fault current of 10kA (symmetrical).21.5RATIOCURRENT(10kA)Current, pu of ime, sec0.050.060.070.08Fig.4. 50:5, C10, CT with a burden of 0.2ohms under fault current of 10kA (fully offset).5 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines1RATIOCURRENT0.80.6Current, pu of 0.8-100.010.020.030.04time, sec0.050.060.070.08Fig.5a. 50:5, C10, CT with a burden of 0.2ohms under fault current up to75kA Current, pu of 0175time, sec0.0180.01850.0190.0195Fig.5b. 50:5, C10, CT with a burden of 0.2ohms under fault current up to75kA (symmetrical).First half-cycle of the secondary current.6 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines2RATIOCURRENT1.5Current, pu of 0.030.04time, sec0.050.060.070.08Fig.6a. 50:5, C10, CT with a burden of 0.2ohms under fault current up to75kA (fully offset).RATIOCURRENT0.250.2Current, pu of 180.019time, sec0.020.021Fig.6b. 50:5, C10, CT with a burden of 0.2ohms under fault current up to75kA (fully offset).First half-cycle of the secondary current.7 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines3550:5 C100.2 ohm burdenSymmetrical CurrentPeak Secondary Current, % of Fault current302520151051020304050Fault Current, kA607080Fig.7a. 50:5, C10, CT with a burden of 0.2ohms: relation between the peak secondary current and peak faultcurrent (symmetrical waveform).2450:5 C100.2 ohm burdenFully Offset CurrentPeak Secondary Current, % of Fault current222018161412108641020304050Fault Current, kA607080Fig.7b. 50:5, C10, CT with a burden of 0.2ohms: relation between the peak secondary current and peak faultcurrent (fully offset waveform).8 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines3. Microprocessor-Based Relays and Saturated Current WaveformsAs explained and illustrated in the previous section, low-ratio CTs pass proportionally lessand less signal energy to the relay when the primary current increases dramatically. In anextreme case of the fault current being 1000 times the CT rating, only a small percent of thiscurrent, in the form of short spikes, would be delivered to the relay. This section explains andillustrates how a typical microprocessor-based relay responds to such waveforms.Response of Instantaneous Overcurrent functions is of primary interest.SECONDARYCURRENTWith reference to Figure 8 a typical relay incorporates input current transformers(galvanic isolation), analog filters (anti-aliasing), A/D converter, magnitude estimator possiblywith digital pre-filtering, and an Instantaneous Over-Current (IOC) comparator.INPUT TIMATORTRIP SIGNALPICKUPSETTINGFig.8. Signal processing chain of a typical relay.3.1. Impact of Relay Current TransformersIn general, the relay input CTs may saturate adding to the complexity of the analysis, andto the scale of the problem. However, saturation of relay input CTs may be neglected for thefollowing reasons:The secondary current is substantially reduced under severe saturation of main CTs.Moreover, saturation of the main CT makes the secondary current symmetrical eliminatingthe danger of exposing the relay input CT to decaying dc components. And thirdly, thesecondary current has a form of short lasting spikes. This limits the flux in the cores of therelay inputs CTs.For example, consider the case of Figure 5. Under say 75kA of symmetrical fault currentthe secondary current is approximately a series of triangular peaks of about 0.08*75kA* 2/ (50:5) 848A secondary, lasting approximately 0.5-1ms. Assuming 1ms duration of thesespikes, the true RMS of this secondary signal is only 120A, or 24 times the 5A rated of therelay input.In reality, the relay input CT would have some impact on the response of the relay.Frequency response, i.e. ability to reproduce the short lasting input signal, may play a role.The theoretical analysis of this paper neglects the impact of relay input CTs it is believedto be small. This is confirmed through testing of actual relay hardware.9 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines3.2. Impact of the Analog FilterAnalog filters are implemented in order to prevent aliasing of higher frequencies on thefundamental frequency signal. Typically, a second order filter is used with a cut-offfrequency of about 1/3rd of the sampling rate.Analog filters have a positive impact on the response of the relay to heavily saturatedcurrent waveforms. Due to its intended low-pass filtering response, the analog filter reducesthe peak values of its input signal and lengthens the duration of such spikes. In a way, theanalog filters smoothes out the waveform by shaving its peaks and moving the associatedsignal energy into the area of lower magnitude. This phenomenon is illustrated in Figure 9.Given the fact that the peak magnitude of spikes is well above the conversion level of therelay, and as such it is not used by the relay when deriving the operating quantity, theoperation of shifting some signal energy from the peaks into the low magnitude area wouldincrease the operating signal, and improve the overall response of the relay.Figure 9 assumes a linear analog filter, i.e. a filter that would not saturate despite of thehigh magnitude of its input. Most filters, however, are designed using active components(operational amplifiers) and will saturate on waveforms such as the one of Figure 9. Figure10 shows response of a simplified model of such filter (clamping of the input signal to alinear filter). As seen in the figure, the signal is reduced even more. What is important, theanalog filter shifts some portion of the signal energy into the low magnitude region when itis measured and utilized by the relay.400300SIGNAL ENERGY SHIFTEDFROM THE AREA THATCANNOT BE USED, TOTHE AREA THAT IS USEDBY THE RELAY200RELAY INPUTCURRENTOUTPUT FROM THEANALOG FILTERCurrent, pu1000-100-200-300-4000.010.020.030.04time, sec0.050.06Fig.9. Impact of a linear analog filter on the saturated current waveform(64kA fault current; C10, 50:5, CT with 0.2ohm burden).10 of 34GET-85010.07

CT Saturation in Industrial Applications – Analysis and Application Guidelines400300SIGNAL ENERGY SHIFTEDFROM THE AREA THATCANNOT BE USED, TOTHE AREA THAT IS USEDBY THE RELAY200RELAY INPUTCURRENTOUTPUT FROM THEANALOG FILTERCurrent, pu1000-100-200-300-4000.010.020.030.04time, sec0.050.060.07Fig.10. Impact of a linear analog filter on the saturated current waveform(a simplified model of a non-linear filter).3.3. Impact of the A/D ConverterThe impact of the A/D converter is twofold. First, any converter has a limited conversionrange where signals above a certain level are clamped. This is similar to the response of theanalog filter in front of the A/D converter (saturation of the amplifiers). The conversion rangeof today’s relays is typically in the 10-50 span. For example, the GE 469 Motor ManagementRelay clamps the inputs at 28.3* 2 *5A 200A secondary peak, assuming the 5A ratedcurrent.Figure 11 illustrates the impact of the A/D clamping on the signal processed by a givenrelay. The second aspect related to the A/D conversion is a limited sampling rate. Today’srelays sample at rates varying from 8 to 128 samples per cycle. Industrial relays tend tosample at 8-16 times per cycle.Given the short duration of the signal pulses produced by a heavily saturated CT, locationof A/D samples on the waveform plays an important role. Consider Figures 12 and 13. InFigure 12 the samples lined up in a way that 3 samples in each cycle “caught” the peaks ofthe signal. In Figure 13 the samples lined up in a way that only 2 samples in each cyclealigned with the peaks. This will result in different values of the operating signal for the IOCfunction. In the analysis, the worst-case must be considered, and in this context, Figure 13presents the worse condition.11 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application GuidelinesIt is also intuitively obvious that higher sampling rates give better chance to “integrate”the short lasting signal pulses and yield a higher operating signal, and thus better relayperformance. This is illustrated in Figure 14 where the sampling is increased from 12 to 16samples per cycle (s/c).400300200RELAY INPUTCURRENTCurrent, pu100OUTPUT FROM THEANALOG FILTERIMPACT OF THELIMITED me, sec0.050.06Fig.11. Impact of the A/D converter – clamping (case of Fig.9).12 of 34GET-85010.07

CT Saturation in Industrial Applications – Analysis and Application Guidelines400300200RELAY INPUTCURRENTCurrent, pu100OUTPUT FROM THEANALOG FILTERSAMPLES ALIGNEDSO 3 SAMPLES IN EACHCYCLE TRACE THEMAXIMUM0-100-200-300-4000.010.020.030.04time, sec0.050.060.07Fig.12. Impact of the A/D converter – sampling (case of Fig.9).400300200RELAY INPUTCURRENTCurrent, pu100OUTPUT FROM THEANALOG FILTERSAMPLES ALIGNEDSO 2 SAMPLES IN EACHCYCLE TRACE THEMAXIMUM0-100-200-300-4000.010.020.030.04time, sec0.050.060.07Fig.13. Impact of the A/D converter – samples aligned differently compared with Fig.12.13 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines400300200RELAY INPUTCURRENTCurrent, pu100OUTPUT FROM THEANALOG FILTERHIGHER SAMPLINGRATE ALLOWS EXTRACTINGMORE SIGNAL ENERGY0-100-200-300-4000.010.020.030.04time, sec0.050.060.07Fig.14. Impact of the A/D converter – higher sampling rate (case of Fig.9).3.4. Impact of the Magnitude EstimatorMicroprocessor-based relays calculate their operating signals, such the currentmagnitude for the IOC function, from raw signal samples. This process of estimation caninclude digital filtering for removal of the dc offset that otherwise would result in anovershoot. Typically a Fourier-type or RMS-type estimators are used.The former extract only the fundamental component from the waveforms (60Hz) througha process of filtering. This would result in a much lower estimate of the magnitude if thewaveforms were heavily distorted.The latter extracts the total magnitude from the entire signal spectrum yielding a higherresponse under heavily saturated waveforms. The difference can be tenfold in extremecases such as the ones considered in this paper.Figure 15 shows an example of the estimation of a true RMS value. Please note that therelay is subjected to 64kA of fault current, and measures “only” 10-15 pu of current (50-75Asecondary, or 500-750A primary). This is only about 1% of the true current, but still 10-15times relay rated current.14 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines5040RELAY INPUTCURRENTOUTPUT FROM THEANALOG FILTER30ESTIMATED, TRUE RMSCURRENT MAGNITUDE20Current, pu100-10SAMPLES-20-30-40-500.010.020.030.04time, sec0.050.060.07Fig.15. Example of amplitude estimation – true RMS algorithm (case of Fig.9).3.5. Impact of the IOC ComparatorThe derived operating current signal is compared against a user set threshold. Extrasecurity may be implemented by requiring several consecutive checks to confirm the trip(“security counters”). This impacts when and for what current the relay would operate.Another aspect is the rate at which the operating conditions are checked. They may beexecuted with each new sample, every other sample, once a cycle, etc. (“protection pass”).This again impacts if and when a given function operates if the current is not steady.Intimate knowledge of the relay inner workings is required to analyze this, as well as thepreviously discussed aspects of the relay response.The next section proposes a methodology for reduction of the many factors impactingresponse of a given relay to waveforms produced by a given CT in order to facilitatepractical analysis and application in the field.4. Method of Quantifying Response of IOC Protection Under CT SaturationThis section presents a methodology for reduction of the many factors impactingresponse of a given relay to waveforms produced by a given CT in order to facilitatepractical analysis and application in the field.15 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application GuidelinesAs shown in the previous subsection, any given relay reduces the signal coming from theCT to a series of pulses. These pulses are further limited in magnitude by the conversionrange of the relay, while their duration is impacted by the natural inertia of the analog inputcircuitry of the relay (input transformers, analog filters). As a result considerable variability isremoved in the A/D samples in response to the CT parameters. Additionally, a typical relayapplies averaging when deriving its operating quantities (such as the true RMS). This reducesvariability even further.The above observation facilitates the following method of quantifying response of anygiven relay to any given CT. The method starts with a portion to be completed by relaymanufacturers as follows:1.Assume a nominal burden of a given CT. Under different burden, a given CT could bealways re-rated by the application engineer based on the known principles.2.Simulate the CT with and without dc offset in the primary current. Assume a typicalX/R ratio for industrial applications (X/R 15). Repeat for different ratios if required.3.Vary the ac component in the primary current from the CT rated value up to 64kA.4.Use a digital model of a given relay, or the actual relay, to find the operating quantityof an IOC function for a given fault current. When simulating, consider the minimummeasured value within the timing spec of the IOC function. When testing the actualhardware, look for consistent operation within the timing specification of the relay.5.Vary the alignment of samples with respect to the waveform in order to get theworst-case scenario. When simulating, explicitly align the samples in differentpatterns. When testing the actual relay, repeat the test several times to make surethe relay operates consistently.6.The value found in step 5 is the highest setting that could be used for the IOCfunction to guarantee operation within the timing specification for a given faultcurrent. This pair of fault current / maximum pickup setting becomes a point on the2D chart.7.Repeat the above for various fault currents. The obtained points constitute acharacteristic for the considered CT and relay.8.Repeat the above for various CTs obtaining a series of characteristics for theconsidered relay.Figure 16 below shows the important signals for a certain relay fed from a 50:5 C10 with0.2ohm burden under the symmetrical fault current of 1kA (or 20 times rated). Please notethat this particular plot is for a burden different than nominal. The Figure shows that therelay would operate for this case within the timing specification as long as the setting isbelow 8pu. The (20pu,8pu) pair becomes a dot on the chart.16 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application GuidelinesFigure 17 shows the same relay and CT under the current of 10kA (or 200 times rated).The Figure shows that the relay would operate for this case within the timing specificationas long as the setting is below 15pu. The (200pu,15pu) pair becomes a dot on the chart.Figure 18 shows the same relay and CT under the current of 50kA (or 1000 times rated).The Figure shows that the relay would operate for this case within the timing specificationas long as the setting is below 14pu. The (1000pu,14pu) pair becomes a dot on the chart.Repeating this for various fault currents, with and without dc offset, while varying thealignment between samples and waveforms, and plotting these as dots on the chart woulddivide the fault current / pickup plane into three regions: solid operation (A), intermittent orslow operation (B), and no operation (C) as depicted in Figure 19.40ESTIMATED, TRUE RMSCURRENT MAGNITUDE(MIN OF ABOUT 8PU)TIMING SPECIFICATION30Current, pu20100-10-20-300.020.040.060.08time, sec0.10.120.14Fig.16. 50:5, C10 CT feeding a relay. Fault current of 1kA (20 times rated).17 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelines100TIMING SPECIFICATION80ESTIMATED, TRUE RMSCURRENT MAGNITUDE(MIN OF ABOUT 15PU)6040Current, pu200-20-40-60-80-1000.020.040.060.08time, sec0.10.120.14Fig.17. 50:5, C10 CT feeding a relay. Fault current of 10kA (200 times rated).100TIMING SPECIFICATION80ESTIMATED, TRUE RMSCURRENT MAGNITUDE(MIN OF ABOUT 14PU)6040Current, pu200-20-40-60-80-1000.020.040.060.08time, sec0.10.120.14Fig.18. 50:5, C10 CT feeding a relay. Fault current of 50kA (1000 times rated).18 of 34GET-8501

B(slow orintermitted)FAULTCURRENT, kACT Saturation in Industrial Applications – Analysis and Application GuidelinesA(solid operation)C(no operation)F2F1PICKUPSETTING, pu100% linePKP1PKP2Fig.19. The concept of “fault current – IOC pickup” curves.The fault current – IOC pickup curves are interpreted as follows: if the CT were perfectlylinear, and the relay had an infinite conversion range, the relay would see exactly 100% ofthe actual primary current, and would operate if the fault current equals the entered IOCsetting. This would constitute a straight line as shown in Figure 19. Due to CT saturation andthe finite relay range, the relay sees less than the actual (ratio current), and thus needs morecurrent than 100% of the setting in order to operate. Therefore, the curves climb up awayfrom the 100% line.If set to PKP1, the relay would operate as long as the fault current is above F1 value(crossing the pickup line), and the fault current is below F2 value (severe saturationdecreasing the relay operating current below the pickup value).If set to PKP2, the relay would never operate, because the operating value never goesabove the PKP2 value: first, the current is to small; next the current is too large causingenough saturation to keep the operating quantity low.Solid (guaranteed) operation of the IOC functions is of primary interest here. Therefore,the left line dividing solid operation form the intermitted operation shall be provided to theusers as shown in Figure 20. Charts for different CTs shall be included on the same graph.19 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application GuidelinesCT-4CT-3BETTERCT-2CT-1RELAY ATYPICAL IOC SETTINGFAULTCURRENT, kAWORSECT-3 is adequatefor the intended settingMAXIMUM FAULT CURRENTIOC SETTING RANGECT-4 is adequatefor any settingCT-2 is not adequatefor the intended settingAll fours CTs areadequate for the typicalIOC settingPICKUPSETTING, puINTENDEDPICKUPSETTINGFig.20. The concept of fault current – IOC pickup curves: Selecting CT for a specific relay, specific maximumfault level and specific pickup setting.The user applies the chart as follows.For an intended pickup level the user reads the fault current from the curve. If a fault ofthis magnitude happens, this particular relay fed from this particular CT would see justenough current to operate. This point defines the boundary of safe operation. If the actualmaximum fault current is below that value, the application is safe; if above, the relay maytrip slow or not at all for currents above the value from the chart.If the application has a problem, the user could use a better CT. A family of curves shallbe provided for various CTs. A CT shall be selected with the characteristic to the right of theintended pickup – maximum fault current point.Please note that given the maximum fault current in Figure 20, CT-4 is adequate for anysetting value (the CT-4 curve is located to the right from the maximum relay setting line). TheCT-4 of this example is the lowest class / ratio CT that does not limit at all application of this20 of 34GET-8501

CT Saturation in Industrial Applications – Analysis and Application Guidelinesparticular relay. Vast majority of CTs of a given series fall into this category, and the curvesare really needed only for the CTs below this borderline case.Please note that given the typical IOC setting of 12pu or so used for short circuitprotection of motors, all four CTs in the example of Figure 20 are adequate (even the CT-1curve is located to the right from the typical setting line).To understand better application of the curves, consider a relay and two CTs as in Figure21. Assume a setting of 19pu is to be used on this particular relay fed from CT-1 on the buswith short circuit capacity of 50kA. Because the 50kA/19pu point is outside the CT-1 curve,this application is not secure. With this setting the relay would operate reliably up to thefault current of 15kA. This CT could be used with settings below 17.5pu.If the 19pu setting is a must, and the short-circuit capacity is 50kA, CT-2 shall be used.It’s curve is to the right of the 50kA/19pu point, meaning the relay would always operate forfaults fed from this bus with a setting of 19pu.Assume the CT-2 is used with this relay: The highe

Kent Jones, Technology Manager, GE Multilin - Instrument Transformers Inc (ITI) 1. Introduction It is possible that relatively low-ratio CTs are applied for protective relaying of small loads fed from switchgear and motor cont