PACKAGE TERMINAL AIR CONDITIONER (PTAC)AND HEAT PUMPSpecifications and Accessories CatalogWise Decision.It’s an Amana brand.Amana is a registered trademark of Maytag Corporation orits related companies and is used under license to GoodmanCompany, L.P., Houston, TX, USA. All rights reserved.Premium Amana Brand QualityFeaturingEDENTMWeb-BasedMonitoring

EDEN A COMBINATION OF ENERGY MANAGEMENTAND PTAC PERFORMANCEThe Amana brand Eden control system brings together our best PTAC and our finest energy management software, whichis now capable of integrating with optional property management and front desk management software. Reduce PTAC energyconsumption up to 35% OR MORE* with features such as the in-unit energy management system, programmable temperature setback, and temperature limiting. The Maintenance Notification System adds value by helping head off potential PTAC service issues.AMANA BRAND EDEN SOLUTION TIERSIN-ROOM – “SELF-INSTALLABLE” WIRELESS PERIPHERALSThe Eden Wireless Remote Thermostat can be mounted on the wallanywhere in the guest room. It is battery poweredand capable of wireless communication withthe PTAC to maintain room temperature. Bestof all, there are no wires to run. The PTAC andthermostat connect at the press of a button andwork in-sync to display accurate temperature.The Eden Wireless Antenna installs inside the PTACwith a snap-in connector like atelephone jack. Installing the antennaallows the PTAC to communicatewirelessly with other devices in theroom and to the Eden network. 60,000 rooms have had wireless installations since 2005 Total wireless devices deployed to date: 425,000 The Eden Occupancy Sensor and Door Switch Combo Devicecompletes the in-room equipment. This infraredsensor can determine when the room is occupied.When empty, it signals the PTAC to adjust thetemperature based on programmable set-backsto save energy.SITE-LEVEL — CENTRAL WIRELESS CONTROLLER Site-wide PTAC ConfigurationSite-wide PTAC DiagnosticsFront-Desk System InterfaceEmail ReportingInternet Accessible Web User Interface Enterprise* These savings represent estimated savings over time as compared to the samePTAC model without the Eden EMS installed and were generated using generalassumptions including energy loads, local weather averages and use of occupancycontrols. Actual savings will vary according to actual use habits, room squarefootage, and how the unit is installed and maintained.www.amana-ptac.comThe Amana brand Eden PTAC with antenna, combinedwith the self-installable, wireless thermostat andoccupancy sensor, give the property owner completecontrol over the equipment settings and can reducePTAC energy usage up to 35% OR MORE.*

EDEN A COMBINATION OF ENERGY MANAGEMENTAND PTAC PERFORMANCEENTERPRISE – MULTIPLE WIRELESS CONTROLLERSCentral Monitoring and Control of Multiple Properties Data WarehousingVirtual MeteringSavings AnalysisLoad SheddingEmail ReportingWEB-BASED MONITORING –AMANA BRAND EDEN CONTROLLERALL PTACS IN A BUILDING CAN BE MANAGED THROUGH A SINGLE INTERFACE ON A PC.Features Include: Full unit details for every PTAC, visible from the frontdesk or home office Automatic emails for PTAC maintenance Ability to change all settings on the unitSet-backsOnce a room is declared unoccupied by the occupancy sensor,the PTAC progresses through three different temperature setbacks, configured as three degree and time pairs. Enhanced diagnostics Monitors up to 250 PTACs WIRELESSLY with one controller Expand the network with additional controllers– System Verification– Site Statistics– Global Setbacks– Email Reporting– EMS Configuration– Unit Health– Site Statistics– Unit Code AlertsUnrented Set-PointsBy integrating with your property’s Front Desk System,the PTACs will adjust to specific set-points when no longeridentified as rented in the system.Example setback configuration:1. 2 , 30 mins –Setback the temp 2 degreesafter 30 minutes2. 4 , 1 hr –Setback the temp 2 more degreesafter 30 more minutes3. 8 , 3 hrs –Setback the temp 4 more degreesafter 2 more hoursTemp LimitingEach PTAC can be configured with a heating and coolingtemperature set-point limit.Specifications and Accessories Catalog3

Standard Features Energy Efficiencies: With EERs up to 13.3 and COPsup to 3.8, our unit’s high efficiencies may qualifyyou for many of the rebates offered by electricalpower companies.Quiet Operation: Our PTAC has been redesigned to bethe quietest PTAC we’ve ever built. The unit’s stateof-the-art design and construction provide a quietenvironment, allowing guests to enjoy peaceful,sleep-filled nights. –– Two fan motors (indoor/outdoor)–– Indoor tangential fan for quiet operation–– STC of 28 4Assembled in the USA for 40 years: assembled at ourplant in Waller, TX, using Goodman resources includingengineering, production, and testing. Increased Dehumidification Capacity: Maintain lowerhumidity levels in rooms while cooling them withoutthe need for expensive add-ons. As a result, guests feelmore comfortable at higher temperatures, thusreducing cooling costs.Seven-Button Touch Pad: Provides complete controlto guests for in-room comfort while maintainingenergy efficiency.Five-Year Limited Warranty: Enjoy one of the mostcomprehensive warranties in the industry: First Year:parts & labor; Second through fifth years: parts& labor on certain sealed system components;second through fifth years: on certain functionalparts only. For complete warranty details, visitwww.amana-ptac.com.100% Run Tested: All units are 100% run tested atour plant in Waller, TX, including leak checks duringmanufacturing and again prior to shipmentat the warehouse.www.amana-ptac.com 7⅝" Unit Front Depth: Enhance valuable roomspace with our slim unit front, which has a sleek7⅝" depth, one of the shallowest silhouettes inthe industry today. In addition, to inhibit guesttampering, the front can be secured to the chassiswith a hidden screw.Easy Pull-Out Filters: Our filters are washable andeasy to maintain.Filter Dryer for Sealed System Refrigerant: Standardin all units to protect the compressor and lengthen thelife of the unit by removing moisture and preventingacid formation.Condensate Dispersion System: Our condensatedispersion system removes condensate from indoorcooling operation by throwing water directly on tothe outdoor coil for rapid evaporation and increasedcooling efficiencies. The slinger ring on the new,enhanced fan draws water up and into the fan blades.This water is then atomized and evaporated into theatmosphere through the condenser. Increased surfacearea from the coil allows more water to be evaporatedon the sides of the coils and helps to minimizecondensate run-off.Front Desk Control: Each unit comes equipped withthe EDEN control and energy management software.Using the EDEN software and optional RF Antenna, allunits can be wirelessly connected to a central hub forenhanced energy savings and diagnostics. Amanabrand PTACs also have a low-voltage interfacecapability with a field-supplied front-desk ON/OFFswitch. (See inside front cover.)

Room Freeze Protection: When the unit sensestemperatures of 40 F or below, the unit activatesthe fan motor and either the electric resistanceheater or the hydronic heater.Easy-to-use Controls: No complex controls to confuseyour guests and create phone calls for your manager.Controls are easy to read, understand, and activate.Our new 7-button control panel provides guests withcomplete control of the unit for their in-room comfortwhile maintaining overall energy efficiency.Easy to Service with On-Board LED Diagnostics:The main components are easily serviced and thereis no guessing to determine the problem with oureasy-to-read diagnostics.Stonewood Room Front: Our Stonewood room frontstrikes the balance between attractive styling andpractical design. Distinctive contours and a modernappearance enhance the character of even the mostluxurious room, while the sleek 7⅝" depth maximizesusable space for your guests.Remote Thermostat Control: When the Eden wirelessremote thermostat (DS01G, sold separately) is set up,both the remote thermostat and unit control panelcontinue to control the unit, providing flexibility andhome-like system control. Installation requires no morethan pressing two buttons. No need to run wires ormake electrical connections.Zero Floor Clearance: The unit can be installed flushto a finished floor, if desired. (Some accessories donot have zero clearance). 30-Second Fan-Off Delay: The fan continues to run30 seconds after the compressor has stopped in eithercooling or heat pump mode and after electric heat hasbeen turned off. This improves efficiency by dispersingthe conditioned air on the coils into the room.Compressor Lock-In: This feature helps prolong the lifeof the compressor by preventing short-cycling. Whenthe compressor is switched from Off to On becauseroom temperature has risen or fallen below thespecified limit, it will remain on for at least 4 minutes.If the temperature set-point is changed during this4 minutes, the lock-in feature is overridden.Automatic Emergency Heat: No more “my unit is notheating” complaints during the middle of the night.Heat pump units will automatically switch over toelectric resistance heat if the heat pump compressorsystem fails or if the heating load is greater than theunit capacity.Constant Fan Mode: Take advantage of each unit’sdual options — select continuous fan operation orcycle the fan ON and OFF with the thermostat.Our 7-button design allows guests to select fanperformance while allowing the owner to have theunit revert to the desired program of continuousfan or cycle with conditioning.Hidden Ventilation Control: The ventilation controllever is hidden from the occupant's view to allow youto manage ventilation requirements.High-Pressure Switch: Protects the unit from highpressure and damage to the unit, helping to ensurelong unit life.Specifications and Accessories Catalog5

gh-Efficiency Cooler PTACHEHHigh- ‐EfficiencyHeatPumpAStandard ModelDRYDehumidCoolerPTACCCorrosion Protection (Seacoast)PMCDigiAIRCoolerPTACDPower Door (not for DigiAir models)PMHDigiAIRHeatPumpPTACELDigiAir Supplemental HeaterHHydronic-Heat BTU/h60Hz1717,000BTU/h60HzLighting ControlQQuiet STC 31 Chassis (not for DigiAir models)RRF AntennaVPower Vent (not for DigiAir models)XPlaceholder* Not all cooling capacities are available for each model typeshown above. See actual data on the following pages foravailable z,1Phase4265V,60Hz,1Phase00 NoElectricHeat15 1.5kWHHigh-EfficiencyR-410A505.0kW* nSeriesR-410A3.5kW(230/208V)3.7kW(265V)25 2.5kW** Not all rated voltages are available for each model type andcooling capacity shown above. See actual data on followingpages for available 0CXXXPTC073*25CQRWPower Cord ConfigurationPower Receptacle ConfigurationPower Cord Plugs250V Rating Power Cord Plugs with LCDI DeviceNEMA 6 Configuration30 amp20 amp15 ampNEMA6-15R; 250Vreceptacle used on230/208V unitsNEMA6-20R; 250Vreceptacle used on230/208V unitsNEMA6-30R; 250Vreceptacle used on230/208V units20 amp6www.amana-ptac.comNEMA7-20R; 277V receptacleused on 265V unitsWWGG277V Rating Power Cord PlugsNEMA 7 Configuration30 ampNEMA7-30R; 277V receptacleused on 265V unitsAll units come with factory-installed power cords.All units less than 250 volts come with LCDI device.

Product Specifications: PTC Models — Cooling/Electric Heat230/208 VoltsModel 6, 8, 9Voltage ³Capacity (BTU/h)Amps ¹⁰Watts ¹⁰EERPTC073G***XXX230 / 2087,000 / 7,0003.1 / 3.1580 / 56012.0 / 12.5PTC093G***XXX230 / 2089,200 / 9,0004.1 / 4.1790 / 76511.6 / 11.7PTC123G***XXX230 / 20811,900 / 11,7005.0 / 5.01045 / 103511.0 / 11.0PTC153G***XXX230 / 20814,800 / 14,5007.0 / 7.01,500 / 1,47010.0 / 10.0PTC173G***XXX230 / 20816,700 / 16,4008.41,725 / 1,7059.7 / 14,8006.01,48010.0Unit without Electric HeaterMin. Circuit Amps 2, 4, 10CFM (Cool/Wet Coil)CFM (Dry Coil)Ventilated Air, CFM (Fan Only)*Dehumidification (Pints/Hr.)Net Weight (lbs.)Ship Weight (lbs.)HighLowHighLow265/277 VoltsModel 1, 6, 8Voltage ¹, ³Capacity (BTU/h)Amps ¹⁰Watts ¹⁰EERUnit without Electric HeaterMin. Circuit Amps 2, 4,10CFM (Cool/Wet Coil)CFM (Dry Coil)Ventilated Air, CFM (Fan Only)*Dehumidification (Pints/Hr.)Net Weight (lbs.)Ship Weight 11934031436033265*4.4113130* Actual vent CFM performance will vary due to application and installation conditions.Notes¹ All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit PTPWHWK4 anddisconnect switch PSHW04A.² Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;maximum is 292 volts.⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must becartridge-style time-delay fuses (included and factory-installed on all Amana brand 265-volt chassis). See heater performance⁵ Heating capacity and efficiency based on unit operation without condensate pump.⁶ Specify two-digit heater kW size to complete model number.⁷ R-410A refrigerant used in all systems.⁸ All units meet or exceed ASHRAE 90.1 standards.⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notationrefers to compressor only.Specifications and Accessories Catalog7

Product Specifications: HEC Models — Cooling/Electric Heat230/208 VoltsModel 6, 8, 9Voltage ³Capacity (BTU/h)Amps ¹⁰Watts ¹⁰EERHEC073H***XXX230 / 2087,000 / 7,0003.6 / 3.6535 / 55512.6 / 13.0HEC093H***XXX230 / 2089,200 / 9,0004.6 / 4.6750 / 77011.8 / 11.9HEC123H***XXX230 / 20811,900 / 11,7005.5 / 5.5990 / 102511.2 / 11.3HEC153H***XXX230 / 20814,800 / 14,5007.3 / 7.31,470 / 1,44010.2 / 1176.339026431028265*3.6102119Unit without Electric HeaterMin. Circuit Amps 2, 4, 10CFM (Cool/Wet Coil)CFM (Dry Coil)Ventilated Air, CFM (Fan Only)*Dehumidification (Pints/Hr.)Net Weight (lbs.)Ship Weight (lbs.)HighLowHighLow* Actual vent CFM performance will vary due to application and installation conditions.Notes¹²³⁴⁵⁶⁷⁸⁹¹⁰8All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delayfuses (included and factory-installed on all Amana brand 265-volt chassis). See heater performanceHeating capacity and efficiency based on unit operation without condensate pump.Specify two-digit heater kW size to complete model number.R-410A refrigerant used in all systems.All units meet or exceed ASHRAE 90.1 standards.All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.www.amana-ptac.com

Product Specifications: PTH Models — Cooling/Heat Pump/Electric HeatModel 1, 6, 8, *AXXXVoltage ¹, ³230 / 208230 / 208230 / 208230 / 2082652652652657,100 / 7,0009,000 / 9,00011,600 /11,40014,200 /14,0007,6009,10012,00014,6005.8 / 5.87.0 / 7.0Capacity (BTU/h)Amps ¹⁰3.9 / 3.94.2 / 4.2Watts ¹⁰650 / 633750 / 7503.13.75.06.16507581,0911,505EER12.0 / 12.411.9 / 12.011.0 / 11.19.9 / 70Ventilated Air, CFM (Fan Only)*65*65*65*65*65*65*65*65*1,090 / 1,090 1,515 / 1,515Unit without Electric HeaterMin. Circuit Amps 2, 4,10CFM (Cool/Wet Coil)CFM (Dry Coil)Dehumidification (Pints/Hr.)1.72.23.64.41.72.23.64.4Net Weight (lbs.)108112115126108112115125Ship Weight (lbs.)123127132143123127132142* Actual vent CFM performance will vary due to application and installation conditions.Notes¹²³⁴⁵⁶⁷⁸⁹¹⁰All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delayfuses (included and factory-installed on all Amana brand 265-volt chassis). See heater performanceHeating capacity and efficiency based on unit operation without condensate pump.Specify two-digit heater kW size to complete model number.R-410A refrigerant used in all systems.All units meet or exceed ASHRAE 90.1 standards.All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.Specifications and Accessories Catalog9

Product Specifications: HEH Models (High-Efficiency Heat Pumps) —Cooling/Heat Pump/Electric HeatModel 1, 6, 8, **XXXVoltage ¹, ³230 / 208230 / 208230 / 208230 / apacity (BTU/h)7,100 / 7,000 9,000 / 9,000 11,600 / 11,400 14,200 / 14,000Amps¹⁰4.1 / 4.14.7 / 4.76.2 / 6.27.4 / 7.4Watts¹⁰595 / 595720 / 7205957301,0401,430EER13.0 / 13.312.7 / 12.71,040 / 1,040 1,440 / 1,44011.5 / 11.510.2 / 0370Ventilated Air, CFM (Fan Only)*65*65*65*65*65*65*65*65*Dehumidification (Pints/Hr.)1.72.23.64.11.72.23.64.1Net Weight (lbs.)107111114125107111114125Ship Weight (lbs.)122126131142122126131142Unit without Electric HeaterMin. Circuit Amps 2, 4,10CFM (Cool/Wet Coil)CFM (Dry Coil)*Actual vent CFM performance will vary due to application and installation conditions.Notes¹²All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit (PTPWHWK4).Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.³ Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses (included and factory-installed on all Amana brand 265-volt chassis).⁵ Heating capacity and efficiency based on unit operation without condensate pump.⁶ Specify two-digit heater kW size to complete model number.⁷ R-410A refrigerant used in all systems.⁸ All units meet or exceed ASHRAE 90.1 standards.⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers tocompressor only.10www.amana-ptac.com

Product Specifications: PMC Models — Cooling/Electric Heat230/208 VoltsModel 6, 8, 9Voltage ³Capacity (BTU/h)Amps ¹⁰Watts ¹⁰EERPMC073G***XXX230 / 2086,800 / 6,7003.3 / 3.3570 / 56012.0 / 12.1PMC093G***XXX230 / 2089,000 / 8,7004.3 / 4.3785 / 76011.6 / 11.4PMC123G***XXX230 / 20811,800 / 11,7005.2 / 5.21,060 / 1,05511.0 / 11.0PMC153G***XXX230 / 20814,500 / 14,4007.0 / 7.01,575 / 1,5309.9 / 5*4.4133148Unit without Electric HeaterMin. Circuit Amps 2, 4, 10CFM (Cool/Wet Coil)CFM (Dry Coil)Ventilated Air, CFM (Fan Only)*Dehumidification (Pints/Hr.)Net Weight (lbs.)Ship Weight (lbs.)HighLowHighLow* Actual vent CFM performance will vary due to application and installation conditions.Notes¹²³⁴⁵⁶⁷⁸⁹¹⁰All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit PTPWHWK4 and disconnect switch PSHW04A.Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delayfuses (included and factory-installed on all Amana brand 265-volt chassis). See heater performanceHeating capacity and efficiency based on unit operation without condensate pump.Specify two-digit heater kW size to complete model number.R-410A refrigerant used in all systems.All units meet or exceed ASHRAE 90.1 standards.All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.Specifications and Accessories Catalog11

Product Specifications: PMH Models — Cooling/Heat Pump/Electric Heat230/208 VoltsModel 6, 8, 9Voltage ³Capacity (BTU/h)Amps ¹⁰Watts ¹⁰EERPMH073G***XXX230 / 2086,900 / 6,7003.7 / 3.7640 / 64011.9 / 12.0PMH093G***XXX230 / 2088,700 / 8,7004.1 / 4.1795 / 79511.7 / 11.8PMH123G***XXX230 / 20811,400 / 11,2005.7 / 5.71,150 / 1,15010.8 / 124G***XXX26512,0005.1115010.4Unit without Electric HeaterMin. Circuit Amps 2, 4, 10CFM (Cool/Wet Coil)CFM (Dry Coil)Ventilated Air, CFM (Fan Only)*Dehumidification (Pints/Hr.)Net Weight (lbs.)Ship Weight (lbs.)HighLowHighLow265 VoltsModel 1, 6, 8Voltage ¹, ³Capacity (BTU/h)Amps ¹⁰Watts ¹⁰EERUnit without Electric HeaterMin. Circuit Amps 2, 4,10CFM (Cool/Wet Coil)CFM (Dry Coil)Ventilated Air, CFM (Fan Only)*Dehumidification (Pints/Hr.)Net Weight (lbs.)Ship Weight 43330245360270652.2132147340245370270653.6135150* Actual vent CFM performance will vary due to application and installation conditions.Notes¹ All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit PTPWHWK4 anddisconnect switch PSHW04A.² Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;maximum is 292 volts.⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must becartridge-style time-delay fuses (included and factory-installed on all Amana brand 265-volt chassis). See heater performance⁵ Heating capacity and efficiency based on unit operation without condensate pump.⁶ Specify two-digit heater kW size to complete model number.⁷ R-410A refrigerant used in all systems.⁸ All units meet or exceed ASHRAE 90.1 standards.⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notationrefers to compressor only.12www.amana-ptac.com

Product Specifications: All Models — Electric Heat Performance(Primary Heating for PTC, HEC, PMC Models; Auxiliary Heating for PTH, HEH, PMH Models; See below for Power Cord Configuration)VoltageElectricHeaterSize (kW)No. ofStages230/208V1.5 / 1.21230/208V2.5 / 2.1230/208V3.5 / 2.9230/208VNominal Heating (BTU/h)TotalWatts6TotalAmpsMin. Circuit MOP4Ampacity² (amps)[email protected] [email protected] [email protected] 265V5,1004,200--1,570 / 1,2956.8 / 6.28.5156-15 P18,5006,800--2,570 / 2,11511.2 / 10.114.1156-15 P112,0009,900--3,570 / 2,93515.5 / 14.119.5206-20 P5.0 / 4.1117,10014,000--5,070 / 4,16022.1 / 20.027.6306-30 5002,5709.712.2157-20 P265V3.71----12,6003,77014.217.9207-20 P265V51----17,1005,07019.223.9257-30 PNotes¹²³⁴⁵⁶⁷⁸⁹¹⁰All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit (PTPWHWK4).Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-styletime-delay fuses (included and factory-installed on all Amana brand 265-volt chassis).Heating capacity and efficiency based on unit operation without condensate pump.Total watts for 15,000 BTU/h models; subtract 20 watts for PT07/09/12Specify two-digit heater kW size to complete model number.R-410A refrigerant used in all systems.All units meet or exceed ASHRAE 90.1 standards.All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.Specifications and Accessories Catalog13

Product Specifications: PTH Models — Reverse-Cycle Heating PerformanceHeatingCapacity ¹Voltage ¹, ³BTU/h G**AXXX230 / 208265230 / 208265230 / 208265230 / 2082656,500 / 6,4006,8008,200 / 8,0008,30010,600 / 10,50011,30013,900 / 13,70013,700Amps ¹⁰3.9 / 3.93.14.2 / 4.23.75.8 / 5.857.0/7.06.1Watts ¹⁰585 / 585585715 / 7007151,085 / 1,0351,0801,350 / 1,3301,340COP ⁵3.5 / 3.43.43.4 / 3.43.43.2 / 3.23.13.0/3.03370370360360370370410410CFM (Dry)Notes¹ All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit (PTPWHWK4).² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt modelsmust be cartridge-style time-delay fuses (included and factory-installed on all Amana brand 265-volt chassis).⁵ Heating capacity and efficiency based on unit operation without condensate pump.⁶ Specify two-digit heater kW size to complete model number.⁷ R-410A refrigerant used in all systems.⁸ All units meet or exceed ASHRAE 90.1 standards.⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.¹⁰ Refer to electric heat performance data for total MCA and recommended overcurrent protection.Amps and Watts notation refers to compressor only.Product Specifications: HEH Models — Reverse-Cycle Heating PerformanceHeatingCapacity ¹Voltage ¹, ³BTU/h H***XXX230 / 208265230 / 208265230 / 208265230 / 2082656,500 / 6,4006,8008,200 / 8,0008,30010,600 / 10,50011,40013,900 / 13,70013,700Amps ¹⁰4.1 / 4.13.64.7 / 4.74.26.2 / 6.25.47.4 / 7.46.4Watts ¹⁰600 / 600600735 / 7157351,085 / 1,0651,0751,440 / 1,4401,430COP ⁵3.8 / 3.73.63.6 / 3.63.53.3 / 3.33.23.1 / 3.13.1360360370370370370410410CFM (Dry)Notes¹ All 265-volt models must use an Amana brand sub-base (PTSB4**E) or an Amana brand hard-wire kit (PTPWHWK4).² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts;maximum is 292 volts.⁴ Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt modelsmust be cartridge-style time-delay fuses (included and factory-installed on all Amana brand 265-volt chassis).⁵ Heating capacity and efficiency based on unit operation without condensate pump.⁶ Specify two-digit heater kW size to complete model number.⁷ R-410A refrigerant used in all systems.⁸ All units meet or exceed ASHRAE 90.1 standards.⁹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord an

order. Examples: G PTC123*50AXXX PTC073*35CRXX H R-410A igh -Efficiency R410A PTC123*50CXXX PTC073*25CQRW AXXX AA 10,11,12,13 PTC 07 3 G 35 HEC High-Efficiency Cooler PTAC DRY Dehumid Cooler PTAC E ** Not all rated voltages are available for each model type and cooling capacity shown ab